Advant Controller 31 / Issued: 03.99
11 Hardware 07 KP 90 R303
8 .1
1.7 Technical data
In general, the details in section 1 ”System data and system structure” of volume 2 of the system description ”Advant
Controller 31” apply as technical data. Supplementary and deviating data is listed below.
1.7.1 General data
Number of serial interfaces 2
Number of parallel interfaces 1 networking interface for connecting to the
Advant Controller 31 basic unit
Operating and error displays 6 LEDs: RUN, ERR, Supply, RxD, TxD, BLK
Conductor cross section for the max. 2.5 mm
2
removable terminal blocks
1.7.2 Power supply for 07 KP 90 R303
Rated supply voltage 24 V DC
Power dissipation typ. 2.5 W
max. current consumption
with rated voltage 210 mA
with a supply voltage of 30 V 170 mA
Protection against reversed terminal connection yes
1.7.3 Serial interfaces RCOM and CONSOLE
Interface standard EIA RS-232 or EIA RS-485 (RCOM only)
Electrical isolation yes, RCOM interface with respect to the rest of the unit
(see also Fig. 5)
Potential differences So that no earthing potential differences arise between
the 07 KP 90 R303 and the peripheral units connected
to RCOM and CONSOLE, the latter are supplied from
the switch-gear cabinet mains socket (also see earthing
connections in Figure 5).
Transmission speed (Baud rate)
RCOM 300...19200 Baud
CONSOLE 9600 Baud
Terminal assignment and description
of the interfaces RCOM, CONSOLE see page 8 onwards
1.7.4 LED displays
LEDs for operating and error displays:
– Supply voltage present (Supply) 1 green LED
– Fatal or serious error occurred (ERR) 1 red LED
– Ready for RCOM communication (running), (RUN) 1 green LED
– Interface signals RxD, TxD 2 yellow LEDs
– Protocol status BLK 1 yellow LED